Advanced settings - AlarmManager-BASIC and -PRO
In the advanced settings, additional functions of the AlarmManager can be activated.
General Settings
Backup folder
The path to the backup of the AlarmManager configurations-file is set here.
Alarm functions
Setup the behavior of the AlarmManager for existing alarms here. The acoustic feedback (buzzers of
AlarmManager and MultiSensors) can be activated or deactivated as needed, except the CO-alarming. A
CO-alarm always triggers all buzzers for the setup buzzer time.
E-Mail & SNMP
For E-Mail alerting an account with or without user access data can be entered. Depending on the E-mail
server, a encryption method might be necessary. When choosing an encryption mode (STARTTLS / SSL) the
required port will be set to the default port. The port can be changed to another one when needed.
Enter the IP-address of the E-Mail server and the senders address here.
Receive the IP-address of the E-Mail server by entering the domain and pressing the button „DNS -> IP“.
With the Kentix-Check-Button a test E-Mail with the E-Mail-Data can be sent.
The AlarmManager supports full SNMP-functionality. Alarms can be sent as traps. Additionally the
AlarmManager can be configured for requests via Network Monitoring systems. For this purpose you can
download a MIB (Management Information Base) for the SNMP-Host.
SNMP-Trap to SMS Gateway
The AlarmManager (PRO only) can send incoming SNMP-Traps as SMS to the configured users.
Therefor a list of permitted hosts can be created in the section „SNMP - Trap to SMS“.
When a SNMP-Trap is received by the AlarmManager, the content of the trap is sent together with the
assigned name to all users that are activated for receiving Always-Active alarms.
Server Monitoring
Define up to 20 servers (BASIC 3 servers) with IP address and the network port to be monitored. A selection
of ports is available via the pulldown-menu, but also a free port can be specified.
The AlarmManager makes cyclic tests, if the specified ports on the servers are available.
The request interval can be set between 60 and 999 seconds. Note that the alarm will first be triggered after
3 fail attempts with the specified interval.
By pressing the Kentix-Check-Button the connection to the server in the selected line can be tested.
NOTE!
The test e-mail is sent to the e-mail-address of the first user. In case of an error please check, whether an
e-mail-address has already been configured for this user. Also take care of possible restrictions (Routing/
Firewalls) in your network and synchronize data like encryption and communication port with the
responsible persons.